    Fluke 355/353 2000A True RMS Clamp Meter

    Rugged, versatile tool for high current applications
    Fluke 355 and 353 digital clamps give users confidence to read reliable true rms readings; ideal current clamps for high currents up to 2000A. Ultra-wide jaws make it easy to grip thick wires that are common in high current applications.Ultra-durable design and CAT IV 600 V, CAT III 1000 V safety certification provide a higher level of user safety for high energy measurements. 

    The inrush current mode allows accurate peak measurements and is therefore ideal for motors and inductive loads. The Model 355 also measures voltage and resistance and is the ideal clamp for engineering, electrical contractors and industrial maintenance electricians.
    Features
    • Reliably handle a wide range of high current applications with measurement ranges up to 2000 A ac + dc true rms, 1400 A ac and 2000 A dc
    • Large 58 mm (2.3 in) jaw for measuring current in thick or multiple wires
    • CAT IV 600 V, CAT III 1000 V safety certification, increased user safety level
    • Inrush current measurement can accurately capture 'boot' surge current
    • Up to 1000 V ac + dc True RMS, 600 V ac and 1000 V dc high voltage measurement range, allowing users to perform multiple tests with just one tool (355 models only)
    • The combination of up to 400K ohms and on-off buzzer makes the meter more convenient for multimeters. (355 type only)
    • Accurate measurement of frequencies up to 1 kHz, ideal for service applications
    • Quickly analyze readings using the min, max, and average functions
    • Large, backlit display makes it easy to view in low-light areas
    • Use the display hold feature to capture readings even when the display cannot be viewed
    • Use a low pass filter to eliminate noise loads and stabilize readings
      

    Technical Parameters
    Electrical technical indicators
    Current measurement: dc and ac, 10 Hz to 100 Hz
    Range  40A  Resolution  10 mA 
    Class A Accuracy  1.5 % Reading + 15 digits 
    Inrush Current Trigger Level  0.50 A Trigger Level of 
    Frequency Filter Off  2.50 A Trigger Level of 
    Frequency Filter On  0.50 A
    Range  400A  Resolution  100 mA 
    Class A Accuracy  1.5 % Reading + 5 digits 
    Inrush Current Trigger Level  5.0 A 
    Frequency Filter Off Trigger Level  2.5 A 
    Frequency Filter On Trigger Level  2.5 A
    Range  2000 A; 1400 ac rms  Resolution  1 A Class 
    A Accuracy  1.5 % Reading + 5 digits 
    Inrush Current Trigger Level  5 A Trigger Level of 
    Frequency Filter Off  8 A Trigger Level of 
    Frequency Filter On  8 A
    Crest factor (50/60 Hz)
    Range  40A  Crest factor *  2 @ 33 A, 2.4 @ 27 A
    Range  400A  Peak Factor*  2 @ 330 A, 2.4 @ 270 A
    Range  2000 A; 1400 ac rms  Crest factor *  2 @ 1000 A, 2.4 @ 833 A
    Current measurement  ac, 100.1 Hz to 1 kHz
    Range  40A  Resolution  10 mA 
    Accuracy > 10 A  3.5 % Reading + 15 digits 
    Inrush Current Trigger Level  0.50 A Trigger Level of 
    Frequency Filter Off  2.50 A Trigger Level of 
    Frequency Filter On  0.50 A
    Range  400A  Resolution  100 mA 
    Accuracy > 10 A  3.5 % Reading + 5-digit 
    Inrush Current Trigger Level  5.0 A 
    Frequency Filter Off Trigger Level  2.5 A 
    Frequency Filter On Trigger Level  2.5 A
    Range  2000 A; 1400 ac rms  Resolution  1 mA 
    Accuracy > 10 A  3.5 % Reading + 5-digit 
    Inrush Current Trigger Level  5 A Trigger Level of 
    Frequency Filter Off  8 A Trigger Level of 
    Frequency Filter On  8 A
    Voltage measurement (type 355 only) dc and ac, 10 Hz to 100 Hz  
    (600 V and 1000 V range over 10 %, up to 660 V and 1100 V respectively)
    Range  4 V  Resolution  1 mV 
    Accuracy  1 % Reading + 10-bit digital 
    frequency filter off trigger level  0.050 V 
    frequency filter on trigger level  0.050 V
    Range  40 V  Resolution  10 mV 
    Accuracy  1 % Reading + 5-bit digital 
    frequency filter off trigger level  0.25 V 
    frequency filter on trigger level  0.25 V
    Range  400 V  Resolution  100 mV 
    Accuracy  1 % Reading + 5-bit digital 
    frequency filter off trigger level  6 V 
    frequency filter on trigger level  6 V
    Range  600 V ac rms  Resolution  1 mV 
    Accuracy  1 % Reading + 5-bit digital 
    frequency filter off trigger level  6 V 
    frequency filter on trigger level  6 V
    Range  1000 V dc  Resolution  1 V  
    Accuracy  1 % reading + 5 digits
    Voltage measurement (type 355 only) ac, 100.1 Hz to 1 Hz  
    (600 V and 1000 V range over 10 %, up to 660 V and 1100 V respectively)
    Range  4 V  Resolution  1 mV 
    Accuracy  3 % Reading + 10-bit digital 
    frequency filter off trigger level  0.050 V 
    frequency filter on trigger level  0.050 V
    Range  40 V  Resolution  10 mV 
    Accuracy  3 % Reading + 5-bit digital 
    frequency filter off trigger level  0.25 V 
    frequency filter on trigger level  0.25 V
    Range  400 V  Resolution  100 mV 
    Accuracy  3 % Reading + 5-bit digital 
    frequency filter off trigger level  6 V 
    frequency filter on trigger level  6 V
    Range  600 V ac rms  Resolution  1 V 
    Accuracy  3 % Reading + 5-bit digital 
    frequency filter off trigger level  6 V 
    frequency filter on trigger level  6 V
    Resistance measurement (type 355 only)
    Range  400 Ω  Resolution  0.1 Ω 
    Accuracy  1.5 % + 5 digits
    Range  4 kΩ  Resolution  1 Ω 
    Accuracy  1.5 % + 5 digits
    Range  40 kΩ  Resolution  10 Ω 
    Accuracy  1.5 % + 5 digits
    Range  400 kΩ  Resolution  100 Ω 
    Accuracy  1.5 % + 5 digits
    On-off buzzer (type 355 only)
       Open when ≤ 30 Ω
       ≥ 100 Ω
    Measuring frequency
    Measuring range  5.0 Hz to 1 kHz
    Resolution  0.1 Hz (15 Hz to 399.9 Hz); 1 Hz (400 Hz to 1 kHz)
    Accuracy – 5.0 Hz to 100 Hz  0.2% + 2 digits
    Accuracy – 100.1 Hz to 1 kHz  0.5% + 5 digits
    Trigger level  Reference current and voltmeter
    General technical indicators
    battery
       Six 1.5 AA (NEDA 15A or IEC LR6)
    Battery life (typical use, backlight off)
       100 hours
    Test line
       Rated up to 1000 V
    weight
       0.814 kg (1.8 lbs)
    Jaw size
       58 mm (2.28 in)
    Dimensions (length x width x thickness)
       300 mm x 98 mm x 52 mm (12 in x 3.75 in x 2 in)
    Security Level
       IEC 61010-2-032, 600 V CAT IV, 1000 V CAT III
    Environmental technical indicators
    Operating temperature
       32 °F to +122 °F (0°C to +50°C)
    Storage temperature
       -4 °F to +140 °F (-20 ° C to +60 ° C)
    Operating humidity
       0 to 95% (no condensation)
    Operating altitude
       2000 m
    Storage altitude
       10,000 meters
    IP rating
       42 (indoor use only)
    Drop test requirement
       1 meter
    EMI, RFI, EMC
       FCC part 15, IEC/EN 61326-1:1997 Class B, IEC/EN 61326:1997 3V/m, performance standard B, EN61325
    Temperature Coefficient
    Current   0.1% of reading (per °C, outdoor, 22 °C to 24 °C)
    Voltage   0.1% of reading (per °C, outdoor, 22 °C to 24 °C)
    Model Name description
    Fluke 355 AC/DC True RMS Clamp Meter, 2000A includes: 
    • 355 clamp table
    • C43 soft carrying case
    • 6 AA batteries
    • TL224 1.5 m silicone rubber test line
    • TP2 test probe
    • AC285 Alligator Clip
    • User manual
    • 3 year warranty
    Fluke 353 AC/DC True RMS Clamp Meter, 2000A, Test Current Only Includes: 
    • 353 clamp table
    • C43 soft carrying case
    • 6 AA batteries
    • User manual
    • 3 year warranty



     

         

     



    TÂN THÀNH CAM KẾT

    • Sản phẩm, hàng hóa chính hãng.
    • Giá cả cạnh tranh.
    • Dịch vụ chăm sóc khách hàng tận tâm.

    Thông Tin Công Ty

    Đã thông báo

     


    THÔNG TIN LIÊN HỆ:
    -------------------------------
    CÔNG TY TNHH THIẾT BỊ CÔNG NGHIỆP TTH
    Trụ sở: số 124 ngõ 79 Yên Hoà-Cầu giấy-HN
    Kinh doanh 1 : 0816.861.515
    Kinh doanh 2 : 0836.861.515
    Kinh doanh 3 : 0926.511.515
    Kinh doanh 4 : 0916.861.515
    Kinh doanh 5 : 0888.868.515
    Kinh doanh 6 : 0917.971.515
    Website: http://tanthanh-automation.com
    Website: http://thietbitudongtanthanh.com
    Website: http://diencongnghieptanthanh.com
    Email: tthkinhdoanh@gmail.com
    Email: tthkinhdoanh01@gmail.com

  • Kết nối với chúng tôi