Graphic details
It is suitable for systems that require high-precision measurement and control. It can replace the amplifier to directly drive the execution mechanism (such as valve position, etc.). It integrates digital instruments and analog instruments. It can perform digital display control (high-brightness LED digital display) and relative analog display (light column display) of measurement signals such as temperature, pressure, liquid level, speed, etc., making the display of measured values clearer and more intuitive. And dual light column display mode can be selected.
★ SWP-LED series PID digital display external given (or valve position) controller type spectrum table
model | Code | illustrate |
SWP-N | □ | □ | □□ | -□ | □ | □ | -□□ | /□□ | -□ | □ | -□ | -□ | New generation of PID self-tuning controller |
Appearance characteristics | D S | | | | | | | | | | | | Horizontal display instrument *1 Vertical display instrument *1 |
Dimensions | 4 7 8 9 | | | | | | | | | | | 96×48mm (horizontal), 48×96mm (vertical) 72×72mm 160×80mm (horizontal), 80×160mm (vertical) 96×96mm |
Control effect | 15 25 | | | | | | | | | | External given control *2 Valve position control (relay forward and reverse control) *3 |
Communication | □ | | | | | | | | | See "Communication Methods" |
Control output mode | □ | | | | | | | | See "Control Output Mode" |
Transmission output mode | □ | | | | | | | See "Transmission output mode" |
PV input type | □□ | | | | | | See Input Type |
SV input type | □□ | | | | | See Input Type |
First alarm mode | □ | | | | See "Alarm Mode |
Second alarm mode | □ | | | See "Alarm Mode |
Feed output | P | | DC24V power supply output |
Power supply | W T | DC24V power supply AC85-260V power supply (switching power supply) AC220V power supply (linear power supply, can be omitted) |
★ SWP-LED series PID light column display external given (or valve position) controller type spectrum table model | Code | illustrate |
SWP-N | T □ | □□ | -□ | □ | □ | -□□ | /□□ | -□ | □ | -□ | -□ | -□ | New generation PID light column display controller |
Dimensions | 8 | | | | | | | | | | | | 160×80mm (horizontal), 80×160mm (vertical) |
Control effect | 15 25 | | | | | | | | | | | External given control *2 Valve position control (relay forward and reverse control) *3 |
Communication | □ | | | | | | | | | | See "Communication Methods" |
Control output mode | □ | | | | | | | | | See "Control Output Mode" |
Transmission output mode | □ | | | | | | | | See "Transmission output mode" |
PV input type | □□ | | | | | | | See Input Type |
SV input type | □□ | | | | | | See Input Type |
First alarm mode | □ | | | | | See "Alarm Mode |
Second alarm mode | □ | | | | See "Alarm Mode |
Feed output | P | | | DC24V power supply output |
Power supply | W T | | DC24V power supply AC85-260V power supply (switching power supply) AC220V power supply (linear power supply, can be omitted) |
Appearance characteristics | X | Horizontal display Vertical display (optional) |
For special models or requirements, please provide the graduation number or reference standard when ordering.★Communication method:
Code | 0 | 2 | 3 | 4 | 8 | 9 |
Communication | No communication | RS-232 | Print port | RS-422 | RS-485 | Special specifications |
★Communication protocol: SWP communication protocol is adopted when leaving the factory.If the user wishes to order a special communication protocol, please indicate this when ordering.Some instruments with printing ports cannot meet the printing function. When ordering, please choose an instrument that can meet the requirements instead.★Control output mode: Selection code | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
Output method | No output | Relay | 4~20mA | 0~10mA | 1~5V | 0~5V | SCR Output | SSR Output | Special specifications | SOT output |
SCR-silicon controlled zero-crossing trigger pulse output SSR-solid-state relay control output SOT-bidirectional thyristor output★Transmission output mode: Selection code | 0 | 2 | 3 | 4 | 5 | 8 |
Output method | No output | 4~20mA | 0~10mA | 1~5V | 0~5V | Special specifications |
★ Input type:
Code | Input Type | Measuring range | Code | Input Type | Measuring range | Code | Input Type | Measuring range |
01 | B | 400~1800℃ | 09 | Pt100.1 | -199.9~320.0℃ | 17 | 30~350Ω | -1999~9999 d |
02 | S | 0~1600℃ | 10 | Cu50 | -50.0~150.0℃ | 18 | Special specifications | User pending |
03 | K | 0~1300℃ | 11 | Cu100 | -50.0~150.0℃ | 19 | 4~20mA square root | -1999~9999 d |
04 | E | 0~1000℃ | 12 | 4~20mA | -1999~9999 d | 20 | 0~10mA square root | -1999~9999 d |
05 | T | -199.9~320.0℃ | 13 | 0~10mA | -1999~9999 d | twenty one | 1~5V square root | -1999~9999 d |
06 | J | 0~1200℃ | 14 | 1~5V | -1999~9999 d | twenty two | 0~5V square root | -1999~9999 d |
07 | WRe3~25 | 0~2300℃ | 15 | 0~5V | -1999~9999 d | twenty three | Switchable input | |
08 | Pt100 | -200~650℃ | 16 | 0~20mA | -1999~9999 d | | | |
★ Note: To switch input, you only need to set the secondary parameters of the instrument. For details, see the "Instruction Manual".★ Alarm method:
Code | N | H | L | G | A | D |
Alarm method | No alarm (can be omitted) | Upper limit alarm | Lower limit alarm | Deviation alarm | Out of deviation alarm | LBA Alarm |