Graphic details
The SWP-LED series single-loop digital/light column display controller uses a microprocessor for control calculations, and can perform highly accurate linear correction measurements on various nonlinear input signals. The instrument integrates digital instruments and analog instruments, and can perform digital display control (high-brightness LED digital display) and relative analog display (light column display) on measurement signals such as temperature, pressure, liquid level, and speed, making the display of measured values clearer and more intuitive, and can choose dual light column display mode.
★ SWP-LED series digital display controller type music score model | Code | illustrate |
SWP- | □ | □ | □□ | -□ | □ | -□□ | -□ | □ | -□ | □ | LED series digital display controller |
Appearance characteristics | C S | | | | | | | | | | Horizontal display instrument *1 Vertical display instrument *1 |
Dimensions | 1 4 7 8 9 | | | | | | | | | 48×48mm 96×48mm (horizontal), 48×96mm (vertical) 72×72mm 160×80mm (horizontal) , 80×160mm (vertical) 96×96mm |
Control effect | 01 03 04 | | | | | | | | Measurement display Three-position control Four-limit control or four-limit alarm output |
Communication | □ | | | | | | | See " Communication Methods " |
Output method | □ | | | | | | See " Control Output Mode " |
Input Type | □□ | | | | | See Input Type |
First alarm mode | N H L | | | | No alarm (can be omitted) Upper limit control / alarm (four limit control / alarm 2H ) *2 Lower limit control / alarm (four limit control / alarm 2L ) *2 |
Second alarm mode | N H L | | | No alarm (can be omitted) Upper limit control / alarm (four limit control / alarm 2H ) *2 Lower limit control / alarm (four limit control / alarm 2L ) *2 |
Feed output | P | | DC24V power supply output |
Power supply | W T | DC24V power supply AC85-260V power supply (switching power supply) AC220V power supply (linear power supply, can be omitted) *3 |
★ Note 1 : C80 and C90 series are 0.8- inch LED displays, S80 , C70 and C40 series are 0.56- inch LED displays , and C10 series are 0.32- inch LED displays.★ Note 2 : Four-limit control or four-limit alarm outputs are four relay control outputs . Users can modify the internal parameters to set the desired control or alarm mode . ( Four-limit control / alarm is only available in T.C80 , S80 and C90 series. 2H represents two upper limit control / alarm, and 2L represents two limit control / alarm ) .★ Note 3 : Light bar display controller SWP-ST803-01-23-HL-X (horizontal table " S " can be omitted) .★Communication method:
Code | 0 | 2 | 3 | 4 | 8 | 9 |
Communication | No communication | RS-232 | Print port | RS-422 | RS-485 | Special specifications |
★Communication protocol: SWP communication protocol is adopted when leaving the factory.If the user wishes to order a special communication protocol, please indicate this when ordering.Some instruments with printing ports cannot meet the printing function. When ordering, please choose an instrument that can meet the requirements instead.★Control output mode:
Selection code | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
Output method | No output | Relay | 4~20mA | 0~10mA | 1~5V | 0~5V | SCR Output | SSR Output | Special specifications | SOT output |
SCR-silicon controlled zero-crossing trigger pulse output SSR-solid-state relay control output SOT-bidirectional thyristor output★Transmission output mode:
Selection code | 0 | 2 | 3 | 4 | 5 | 8 |
Output method | No output | 4~20mA | 0~10mA | 1~5V | 0~5V | Special specifications |
★ Input type:
Code | Input Type | Measuring range | Code | Input Type | Measuring range | Code | Input Type | Measuring range |
01 | B | 400~1800℃ | 09 | Pt100.1 | -199.9~320.0℃ | 17 | 30~350Ω | -1999~99999 d |
02 | S | 0~1600℃ | 10 | Cu50 | -50.0~150.0℃ | 18 | Special specifications | User pending |
03 | K | 0~1300℃ | 11 | Cu100 | -50.0~150.0℃ | 19 | 4~20mA square root | -1999~99999 d |
04 | E | 0~1000℃ | 12 | 4~20mA | -1999~99999 d | 20 | 0~10mA square root | -1999~99999 d |
05 | T | -199.9~320.0℃ | 13 | 0~10mA | -1999~99999 d | twenty one | 1~5V square root | -1999~99999 d |
06 | J | 0~1200℃ | 14 | 1~5V | -1999~99999 d | twenty two | 0~5V square root | -1999~99999 d |
07 | WRe3~25 | 0~2300℃ | 15 | 0~5V | -1999~99999 d | twenty three | Fully switchable input | |
08 | Pt100 | -200~650℃ | 16 | 0~20mA | -1999~99999 d | | | |
★ Note: To switch input, you only need to set the secondary parameters of the instrument. For details, see the "Instruction Manual".★ Note 3: C70 and C10 have no frequency signal input. The factory default is switching power supply.