2 . Technical Parameters
2.1 Frequency response: 10 ~ 1000 Hz * or 4.5 ~ 1000 Hz (special instructions)
2.2 Natural frequency: 10Hz
2.3 Measuring range: speed 0-20mm/s (optional)
2.4 Output current: 4~20mA
2.5 Output impedance: ≤500Ω
2.6 Working voltage: &;10%
2. 7 Wiring method: two-wire system
2.8 Measuring direction: universal
2.9 Operating environment: temperature -40℃~100℃, relative humidity ≤90%
2.10 Overall dimensions: φ30×70mm
2.11 Installation thread: M10×1.5×15mm (depth)
2.12 Weight: about 300g
3 . Install
3.1 Installation position: Install vertically or horizontally on the vibration point to be measured, fix the M10×1.5×10 screws at the bottom of the sensor to the shell being tested, and then tighten the sensor on it.
3.2 Installation dimensions and specifications: Refer to Figure 1. If the installation position of the transmitter is washed by high-temperature steam, protective measures must be taken to reduce the ambient temperature of the transmitter. Under normal circumstances, no protection is required.
3.3 Wiring instructions: The brown wire is connected to the positive terminal of the DC24V power supply, and the blue wire is connected to the negative terminal of the DC24V power supply. At the same time, the brown and blue wires are also 4~20mA output leads. The connecting wires are required to have good insulation properties and use two-core shielded cables.