Technical Parameters						| Ambient temperature | -40 °C ~+85 °C | 
					| Power supply voltage, DC | 7.2 ~ 35VDC | 
					| Maximum offset | 50% of the selected maximum | 
					| Internal consumption | 25mW ~ 0.8W | 
					| Cold junction temperature compensation | < ±1.0 °C | 
					| Signal range | 4 ~ 20mA | 
					| Minimum signal range | 16mA | 
					| Reaction time | 1 to 60s | 
					| Update time | 440ms | 
					| Load Resistance | ≦(Vsupply-7.2)/0.023Ω | 
					| Minimum span | 5mV | 
					| Input resistance | 10M Ω   | 
	
Technical Parameters
General specifications:
Ambient temperature
-20 ° C ~ +60 ° C
Supply voltage universal
21.6 to 253 VAC, 50 to 60 Hz or 19.2 to 300 VDC
Reaction time
0.4 to 60s
Protection level
IP65
enter
Current input:
Measuring range
-1~25mV
Programmable, measuring range
0 to 20, 4 to 20 mA
Input resistance
Nom.20Ω+PTC25Ω
Voltage input:
Measuring range
-20 mV to 12VDC
Programming, measurement range
0 to 1/0, 2 to 1/0 to 10/2 to 10 VDC
Input resistance
Nom.10MΩ
Output:
display:
Display readout
-1999~9999 (four digits)
Decimal point
Programmable
Digital height
13.8mm
Show upgrade
2.2 times / sec
Inputs outside the input range are displayed in descriptive text
Current output:
Signal range
0~20mA
Programmable signal range
0~20/4~20/2~0/20~4mA
Load (maximum)
20mA / 800Ω / 16VDC
Load stability
<±0.01%of span/100Ω
Relay output:
Relay function
location point
Hysteresis
0.1 to 25% / 1 to 2999
Switch delay
0 to 3600s
Sensor error detection
Make/Break/Hold
Maximum voltage
250VRMS
Maximum current
2A/AC
Maximum AC power
500VA
24VDC maximum current
1A
 
temperature range  
-20°C to +60°C  
General parameters  
voltage  
 7.2...35 V 
 
Internal power consumption  
 25 mW...0.8 W  
 
Voltage drop 7.2 VDC  
Isolation voltage, test  
 1.5KVAC/250VAC  
 
Preheat time  
 5 minutes  
 
 
Communication interface  
Response time  
 1...60s  
 
EEprom error check  
 < 3.5 s  
 
Signal input dynamic 18bit  
Signal output dynamics  
 16bit  
 
General standard
 
Input type
 Absolute precision
 Temperature Coefficient  
 
All ≤±0.05% span < ±0.01% span / °C  
 
Basic standard
 
Input type
 Basic accuracy  
 
Volt ≤ ±10 μV ≤ ±1 μV / °C  
 
TC type: E, J, K, L, N, T, U ≤ ± 1 ° C ≤ ± 0.05 ° C / ° C  
 
TC type: R, S, W3, W5, LR ≤ ± 2 ° C ≤ ± 0.2 ° C / ° C  
 
Signal/noise ratio  
 >60 decibels  
 
 
Electromagnetic compatibility anti-jamming effect  
 <±0.5% span  
 
NAMUR NE 21, standard, burst  
 <±1% span  
 
Calibration temperature 20...28°C  
vibration  
 IEC 60068-2-6 Test FC  
 
Lloyd's Code no.1  
 4 g / 2...100 Hz  
 
Maximum diameter  
 1x1.5 mm2 steel strand  
 
 
Relative humidity < 95% RH (non-cond.)  
Dimensions Φ 44 x 20.2 mm  
Protection level IP68/IP00  
weight  
 50g  
 
Electrical specifications, enter the maximum offset 50% of the maximum  
Thermocouple input
 
Type Minimum Temperature Maximum Temperature Minimum Span Benchmark  
B 
 400°C 1820°C 100°C IEC584  
E -100°C 1000°C 50°C IEC584  
J -100°C 1200°C 50°C IEC584  
K -180°C 1372°C 50°C IEC584  
L -100°C 900°C 50°C DIN 43710  
N -180°C 1300°C 50°C IEC584  
R -50°C 1760°C 100°C IEC584  
S -50°C 1760°C 100°C IEC584  
T -200°C 400°C 50°C IEC584  
U -200°C 600°C 50°C DIN 43710  
W3 0°C 2300°C 100°C ASTM E988-90  
W5 0 ℃ 2300 ℃ 100 ℃ ASTM E988-90  
LR -200°C 800°C 50°C GOST 3044-84  
Cold junction temperature compensation
 
 < ±1.0°C