| Inverter model N2-□□□-×× | 2P5 | 201 | 202 | 203 | 205 | 208 | 210 | 215 | 220 | 230 |
| Horsepower (HP) | 0.5 | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 30 |
| Applicable motor capacity KW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | twenty two |
| Rated current A | 3.1 | 4.5 | 7.5 | 10.5 | 17.5 | 26 | 35 | 49 | 64 | 87 |
| Rated capacity KVA | 1.2 | 1.7 | 2.9 | 4.0 | 6.7 | 9.9 | 13.3 | 18.7 | 24.4 | 87 |
| Weight (Kg) | 1.4 | 1.4 | 2.5 | 4.0 | 4.0 | 6.8 | 7.1 | 11.3 | 11.7 | 33.2 |
| Allow instantaneous stop time (seconds) | 1.0 | 1.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 |
| Input voltage (50/60Hz±5%) | Single-phase or three-phase 200~240V 10%, 50/60HZ 5%, 205 (inclusive) or more for three-phase input |
| The output voltage | Three-phase 200~240V (corresponding to input voltage) |
| control method | Approximate sine wave PWM control |
| Inverter model N2-□□□-×× | 401 | 402 | 403 | 405 | 408 | 410 | 415 | 420 | 430 | |
| Horsepower (HP) | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 30 | |
| Applicable motor capacity KW | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | twenty two | |
| Rated current A | 2.3 | 3.8 | 5.2 | 8.8 | 13 | 17.5 | 25 | 32 | 48 | |
| Rated capacity KVA | 1.7 | 2.9 | 4.0 | 6.7 | 9.9 | 13.3 | 19.1 | 24.4 | 36.6 | |
| Allow instantaneous stop time (seconds) | 1.0 | 1.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 | |
| Weight (Kg) | 2.4 | 2.5 | 3.8 | 4.0 | 7.0 | 7.3 | 12.3 | 12.5 | 13.5 | |
| Input voltage (50/60Hz±5%) | Three-phase 380 ~ 480V ± 10% |
| The output voltage | Three-phase 380 ~ 480V (corresponding to input voltage) |
| control method | Approximate sine wave PWM control |
The frequency of the control system | range | 0.1~400Hz |
| Precision | Digital formula: 0.01% (-10 ~ 40 °C); analog: 0.4% (25 10 ° C) |
| Set resolution | Digital type: 0.01Hz (Note 1); Analog: 0.06Hz / 60Hz |
| Output resolution | 0.01Hz |
| Keyboard frequency setting method | Can be set directly with ▲▼ or with the knob (VR) on the keyboard. |
| External signal setting method | 1. External variable resistor / 0-5V / 0-10V / 0-20mA / 5-0V / 10-0V / 20-0mA 2. With the terminal block (TM2) multi-function contact for rise / fall control or speed Control or program automatic control |
| Other functions | Frequency upper/lower limit, starting frequency, three-stage skip frequency can be set individually |
A general control system | Carrier frequency | 1-12KHz |
| Acceleration and deceleration control | 2-stage acceleration/deceleration time (0.1-3600 seconds) and 2-segment S-curve |
| Voltage/frequency curve | 1 programmable curve, 18 fixed curves |
| Torque control | Torque boost level can be set |
| Multi-function input | 16 functions, 32 options |
| Multi-function output | 6 functions, 12 options |
| Other functions | Automatic voltage adjustment (AVR), slip compensation, deceleration stop or natural stop, automatic reset and restart, brake frequency / voltage / time can be activated by SPESESEARCH or general mode, 3 WIRE operation control. |
| Protective function | Overload protection, over voltage, under voltage, instantaneous power failure restart, acceleration/deceleration/running stall prevention; inverter output short circuit protection, initial ground protection + zero phase CT protection, heat sink overheat protection; over torque detection, fault Contact control, reverse limit, direct start and fault reset after power on, parameter lock |
| Operating keyboard | Can display frequency / speed / line speed / DC voltage / output voltage / current / inverter steering / inverter parameters / fault record / program version |
| Communication control | 1. Can communicate by RS232 or RS485 (need to be used with accessories) 2. Can be used for 1 to 1 or 1 to many (RS485) |
| Operating temperature | -10~40°C |
| humidity | 0 to 95% relative humidity (no condensation) |
| vibration | Below 0.5G |
| LVD specification | EN50178 |
| Protection level | IP 20/NEMA4 (10Hp (inclusive) below) |
| Security Level | UL 508C |
Note 1: The resolution above 100Hz is 0.1Hz when controlled by the operation panel; when it is controlled by computer (PC) or programmable controller (PLC), it can be up to 0.01Hz Note 2:200V level N2-205 (including ) No EMC specifications above |