WS90602 Thermocouple Fully Isolated Dual Output Signal Conditioner
| |  | | (Double output temperature transmission) WS90602 Thermocouple fully isolated dual output signal regulator can be used directly with thermocouples such as K, J, S, E; cold junction compensation function, linearization; DIN T rail. | Input / output range: Tail 1 | Input | Tail 2 | Output 1 | Output 2 | A | 0-400 ℃ | 3 | 4-20mA | 4-20mA | B | 0-600 ℃ | 4 | 0-20mA | 0-20mA | C | 0-800 ℃ | 5 | 1-5V | 1-5V | D | 0-1000 ℃ | 6 | 4-20mA | 1-5V | IS | 0-1200 ℃ | | | | S | User specific specification | User specific specification | User specific specification | User specific specification | Note: Tail 1 indicates the thermocouple model such as (K, J, S...) | | | | | The main technical parameters: Input resistance | ≥100KΩ | Output load resistance RL | Current type 250Ω (typ) | accuracy | 0.3% (for temperature) | Broken state | Output is minimum | Temperature Coefficient | <150ppm/℃ | range of working temperature | 0-50 ℃ | isolation | Input, output, power, four port isolation | Insulation resistance | >100MΩ(500VDC) | Dielectric strength | 1000VDC/1 minute | power supply | 24VDC ± 10% | Power consumption current | <65mA | Broken state | Output minimum | | | Ordering Guide: WS90602□□□ Example: WS90602KA6, that is, the input is K-type thermocouple measurement range 0-400 °C, output 1 is 4-20 mA, output 2 is 1-5V  | | | |