Trang nhất
Thiết bị công nghiệp, tự động hóa
Relay (Rơ le) TRS 230VAC RC 1CO Weidmüller relay 1122840000
Đăng ngày 09-11-2023 06:19:57 PM - 231 Lượt xem
Mã sản phẩm: S004923
Relay (Rơ le) TRS 230VAC RC 1CO Weidmüller relay 1122840000
Ordering data |
type | TRS 230VAC RC 1CO |
Order number | 1122840000 |
Version | TERMSERIES, Relay module, Number of contacts: 1 change-over contacts AgNi, Rated control voltage: 230 V AC ±10 %, Continuous current: 6 A, Screw connection |
GTIN (EAN) | 4032248905034 |
Minimum number of packages | 10pc(s). |
|
Dimensions and weight |
width | 6.4 mm |
Width (inches) | 0.252 inch |
high | 89.6 mm |
Height (inches) | 3.528 inches |
deep | 87.8 mm |
Depth (inches) | 3.457 inches |
net weight | 34g |
|
temperature |
humidity | 5 to 95% relative humidity, Tu = 40°C, non-condensing |
Operating temperature | -40 °C...60 °C |
storage temperature | -40 °C...85 °C |
|
enter |
Rated control voltage | 230V AC ±10% |
AC rated current | 10.1 mA |
rated power | 2.3VA |
Pick-up/release voltage, typical | 145 V / 85 V AC |
Pick-up/release current, typical | 9.13 mA / 4.78 mA AC |
Status Display | Green LED |
protect the circuit | RC element |
RC filter | 94Ω/100nF |
|
output |
Rated switching voltage | 250VAC |
Maximum switching voltage, AC | 250 V |
Maximum switching voltage, DC | 250 V |
continuous current | 6A |
Inrush current | 20/20 ms |
Maximum AC switching capacity (resistive) | 1500VA |
Maximum DC switching capacity (resistive) | 144W@24V |
action delay | < 22 ms |
Off delay | < 30 ms |
Minimum switching power | 1 mA @ 24 V, 10 mA @ 12 V, 100 mA @ 5 V |
Maximum switching frequency at rated load | 0.1 Hz |
|
Contact data |
Number of contacts | 1 |
Contact design | changeover contact |
Contact material | AgNi |
Mechanical service life | 5 x 10 6 switching cycles |
|
Basic Information |
Flame retardant, etc. comply with UL 94 | V-0 |
|
Insulation design |
Rated voltage | 300 V |
Creepage and clearance distances input - output | ≥ 5.5mm |
Dielectric strength input-output | 4kVeff / 1min |
Dielectric strength of mounting rails | 4 kV eff / 1 minute |
Dielectric strength of open contacts | 1kVeff / 1min |
Impact resistance and pressure resistance | 6 kV (1.2/50 μs) |
Protection, etc. | IP20 |
pollution etc. | 2 |
Overvoltage, etc. | III |
|
Detailed standards and certification status |
standard | EN 50178, EN 55011, EN 61000-6-1, 2, 4 |
Certificate number (GERMLLOYD) | 47053-12 |
Certificate number (cULus) | E141197 |
|
Join parameters |
Wire connection method | screw connection |
Bare wire length at rated connection | 8mm |
Maximum tightening torque | 0.4 Nm |
Crimping range at rated connection | 1.5mm2 |
Minimum crimping area | 0.14mm2 |
Maximum crimping area | 2.5mm2 |
Minimum crimping area of wire AWG | AWG 26 |
Maximum crimping area of wire AWG | AWG 14 |
Minimum crimp area for single-strand conductors | 0.14mm2 |
Maximum cross section of single conductor | 2.5mm2 |
Minimum crimping area for flexible conductors | 0.14mm2 |
Maximum crimping area for flexible conductors | 2.5mm2 |
Minimum crimping area for flexible conductors with plastic sheathed tubular ends (DIN 46228/4) Rated connections | 0.25mm2 |
Maximum crimping area Flexible conductor tubular end with plastic sleeve (DIN 46228/4), rated connection | 2.5mm2 |
Minimum crimping area for flexible conductors with tubular ends (DIN 46228-1) | 0.25mm2 |
Maximum crimping area for flexible conductors with tubular ends (DIN 46228-1) | 2.5mm2 |
Minimum crimping area for stranded flexible conductors (two-wire) | 0.5mm2 |
Maximum crimping area for stranded flexible conductors (double wire) | 1mm2 |
Screwdriver tip size | Size PH0 |
Measuring gauge according to standard 60 947-1 | A1, B1 |
|
Rated dataUL |
Maximum ambient temperature (during operation) | 60°C |
Wiring area AWG, min. | AWG 26 |
Wiring area AWG, max. | AWG 14 |
Wire type | Copper hard wire, Copper soft wire |
Maximum tightening torque | 0.4 Nm |
pollution etc. | 2 |