product descriptionThe QUINT POWER power supply
QUINT POWER circuit breakers provide maximum functionality and can be quickly thermally decoupled at six times the rated current, providing selective system protection and cost savings. Precautionary function monitoring ensures extremely high system availability because it can issue critical operating status reports before a fault occurs.
With the static power reserve POWER BOOST, heavy loads can be reliably started. The adjustable voltage covers all ranges between 5 V DC ... 56 V DC.
size
width | 69 mm |
height | 130 mm |
depth | 122 mm |
Spare terminal width | 122 mm |
Spare terminal height | 130 mm |
Alternate assembly view | 72 mm |
Environmental conditions
Protection level | IP20 |
Ambient temperature (running) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (debug type test) | -40 °C |
Ambient temperature (storage/transportation) | -40 °C ... 85 °C |
Maximum relative humidity allowed (operating) | 95% (25°C, no condensation) |
Anti-interference | EN 61000-6-2:2005 |
Installation height | 5000 m |
Input data
Rated input voltage range | 3x 400 V AC ... 500 V AC |
Input voltage range | 3x 320 V AC ... 575 V AC |
| 2x 360 V AC ... 575 V AC |
| 450 V DC ... 800 V DC |
AC frequency range | 45 Hz ... 65 Hz |
DC frequency range | 0 Hz |
PE discharge current | < 3.5 mA |
Electricity consumption | 3x 1.6 A (400 V AC) |
| 3x 1.3 A (500 V AC) |
| 0.9 A (600 V DC) |
Rated power consumption | 517 W |
Shock surge current | < 20 A (typical) |
Power failure bypass | > 20 ms (400 V AC) |
| > 30 ms (500 V AC) |
Choose the right fuse | 6 A ... 16 A (AC: Characteristics B, C, D, K) |
Protection name | Transient surge protection |
Protection circuit/component | Varistor, gas discharge tube |
Output Data
Rated output voltage | 24 V DC ±1 % |
Setting range of output voltage (U Set ) | 18 V DC ... 29.5 V DC (> 24 V DC, stable capacity limit) |
Rated output current (I N ) | 20 A (-25 °C ... 60 °C, U OUT = 24 V DC) |
POWER BOOST (I Boost ) | 26 A (-25 ° C ... 40 ° C constant, U OUT = 24 V DC ) |
Selective fuse (I SFB ) | 120 A (12 ms) |
attenuation | 60 °C ... 70 °C (2.5%/K) |
Even | Yes, for redundancy and increased capacity |
Concatenation | Yes |
Control deviation | < 1 % (load change, static 10% ... 90%) |
| < 3% (load change, dynamic 10% ... 90%) |
| < 0.1 % (the input voltage varies by ±10%) |
Residual wave | < 40 mV SS (rated value) |
Output Power | 480 W |
Typical response time | < 0.16 s |
Peak switching voltage rated load | < 40 mV SS (20MHz at rated value) |
Maximum idle power consumption | 11 W |
Maximum rated load power loss | 40 W |