Trang nhất
Thiết bị công nghiệp, tự động hóa
Bộ nguồn Phoenix,Phoenix power module QUINT-100-240AC/24DC/10 Article No. 2938604
Đăng ngày 31-01-2019 04:50:55 PM - 486 Lượt xem
Mã sản phẩm: QUINT-100-240AC/24DC/10 Article No. 2938604
product description
The QUINT POWER power supply
QUINT POWER circuit breakers provide maximum functionality and can be quickly thermally decoupled at six times the rated current, providing selective system protection and cost savings. Precautionary function monitoring ensures extremely high system availability because it can issue critical operating status reports before a fault occurs.
With the static power reserve POWER BOOST, heavy loads can be reliably started. The adjustable voltage covers all ranges between 5 V DC ... 56 V DC.size
width | 85 mm |
height | 130 mm |
depth | 125 mm |
Spare terminal width | 122 mm |
Spare terminal height | 130 mm |
Alternate assembly view | 88 mm |
Environmental conditions
Protection level | IP20 |
Ambient temperature (running) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transportation) | -40 °C ... 85 °C |
Maximum relative humidity allowed (operating) | 95% (25°C, no condensation) |
Anti-interference | EN 61000-6-2:2005 |
Input data
Rated input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 85 V AC ... 264 V AC |
| 90 V DC ... 350 V DC |
AC frequency range | 45 Hz ... 65 Hz |
DC frequency range | 0 Hz |
PE discharge current | < 3.5 mA |
Electricity consumption | Approximately 2.34 A (120 V AC) |
| Approximately 1.2 A (230 V AC) |
Rated power consumption | 264 W |
Shock surge current | < 15 A (typical) |
Power failure bypass | > 50 ms (120 V AC) |
| > 50 ms (230 V AC) |
Input fuse | 6.3 A (slow blow, internal) |
Choose the right fuse | 10 A ... 16 A (characteristics B, C, D, K) |
Protection name | Transient surge protection |
Protection circuit/component | Varistor |
Output Data
Rated output voltage | 24 V DC ±1 % |
Setting range of output voltage (U Set ) | 22.5 V DC ... 28.5 V DC |
Rated output current (I N ) | 10 A (up to 60 °C) |
POWER BOOST (I Boost ) | 15 A |
attenuation | 60 °C ... 70 °C (2.5%/K) |
Even | Yes, for redundancy and increased capacity |
Concatenation | Yes |
Maximum capacitive load | unlimited |
Active current limit | Ca. I BOOST =15A (in case of a short circuit) |
Control deviation | < 1 % (load change, static 10% ... 90%) |
| < 2 % (load change, dynamic 10% ... 90%) |
| < 0.1 % (the input voltage varies by ±10%) |
Residual wave | < 60 mV SS (rated value) |
Output Power | 240 W |
Typical response time | < 1 s |
Peak switching voltage rated load | < 60 mV SS (20 MHz) |
Maximum idle power consumption | < 2 W |
Maximum rated load power loss | < 24 W |
Overview
net weight | 1.3 kg |
Working voltage display | Green LED |
effectiveness | > 91 % |
Insulation voltage input / output | 4 kV AC (type test) |
| 2 kV AC (conventional test) |
Insulation voltage input / PE | 3.5 kV AC (type test) |
| 2 kV AC (conventional test) |
Insulation voltage output / PE | 500 V DC (conventional test) |
Protection level | I (with PE connection) |
| IP20 |
MTBF (IEC 61709, SN 29500) | > 500000 h |
Installation location | Horizontal DIN rail NS35, EN60715 |
Assembly instructions | Can be installed side by side: horizontal spacing 0 mm, vertical spacing 50 mm |