Second, the main technical parameters
(1) BWY (WTYK) - 803, 802 type
1, normal working conditions: ambient temperature -20 ° C ~ +55 ° C
Relative humidity 5%~95%
2. Measurement range: (0-100) °C (0-120) °C (0-150) °C
3, indicating accuracy: 1.5
4, temperature measuring parts: temperature package dimensions (Φ14 × 150) mm, the material is stainless steel, mounting thread M27 × 2
5. Switching performance: Setting range: full scale Setting accuracy: ±3°C Switching difference: (6±2) °C
Rated power: AC 250V 3A DC 250V 50W
Standard set point: 803 K1=55°C K2=65°C K3=80°C
802 K1=55°C K2=80°C
6, instrument installation size: compatible with WTYK-02.
7. Outdoor performance: The waterproof and waterproof performance of the thermostat meets the requirements of IP55 in GB4208-93.
(B) BWY (WTYK) - 803, 802 (TH) type
1~6 with the same
Outdoor performance: in line with GB/T2433.3-93 "Electrical and electronic products basic environmental test specifications test Ca:
Constant Damp Heat Test Method" Mildew resistance of exposed parts.
(3) BWY (WTYK) - 803, 802A (TH)
Same as above, with Pt 100 platinum resistance output.
XMT series thermometer
1. Display method: three and a half digits
2. Display error: ± (0.5% F.S + 1 word) ± (1% F.S + 1 word) second file
3. Set point deviation: less than ± 1% FS
4. Control point insensitive area: less than ±0.5% FS
5. Output signal error: less than ±1% FS
6. Output contact capacity: AC220V 3A (resistive load)
7. Temperature coefficient: deviate from 20 °C ± 2 °C in the range of 0 °C - 50 °C
Its temperature coefficient is less than 0.05% / °C
8. Industrial power supply: 220V ± 10% 50Hz, power consumption is less than 5W
9. Working environment: non-corrosive gas with temperature 0°C-50°C and relative humidity≤85%
10. Dimensions: 160 × 80 × 150 opening size: 152 +1 × 76 +1
11. Weight: about 3kg