Dung cụ hiệu chuẩn cầm tay, HART375 handheld communicator
				
							Đăng ngày 20-01-2019 09:04:56 PM - 1229 Lượt xem
						
						
							Mã sản phẩm: HART375
						
				HART375 Communicator        
performance
    Fully compliant with the HART ® protocol generic commands products, three AAA alkaline batteries ornickel at, nickel metal hydride rechargeable battery, continuous operation for 13 hours.
 Technical indicators
    The HART 1. ® interface conforming HCF (HART Communication Foundation) protocol, two-way half-duplex 1200bit / s working mode
    The HART 2. ® common mode voltage may be received by the interface of plus or minus 40V
    3. Leakage current is typically less than 1uA@20°C
    4. HART ® interface communication distance <1500m
    5. Isolation mode: isolation between HART communication interface and power supply
    6. Isolation withstand voltage: 500Vrms
    7. LCD screen: 8 lines, 21 words per line
 Physical size
   228mm* 98mm * 60mm (handheld part is 70mm wide * 37mm thick)
 Environmental requirements
    1. Operating temperature range: 0 ° C - +50 ° C
    2. Storage temperature range: -20 ° C - +55 ° C
 Features
    HART ® handset can connect any 4-20mA current loop via HART ® compatible device, the current loop must exist a minimum load resistance of 250Ω. The HART handheld uses the high-frequency digital signal Bell202 frequency shift keying (FSK) technology, which can be superimposed on the 4-20mA current signal for transmission. Handheld with HART ® compatible communications equipment does not affect the 4-20mA analog signal.
 
				
													
				
			 
			
			
		 
		
			
			
Supported transmitter types
    HK-H3151 , HK-H1151 , HK-H990-CT1 , HK-H610 , YOKOKAWA  EJA , Rosemount 1151 , Rosemount 305 1 ,HK-H990M ( HART Universal Pressure Change Round Card) , HK-H991M (General Pressure Transmitter Board) Card) , HK-H3351M (Huakong 3351 Pressure Change Circular Card) , WT-2000 ( Wailai WT2000 Pressure Gauge) ,MV-2000 ( Welltech MV2000 Pressure Gauge) , SIPART_PS2 ( SIMENS Valve Positioner) , SITRANS_FM_MAG (SIMENS Mass flow meter) , SITRANS_TH300 ( SIMENS thermometer) .